کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
764968 1462838 2016 13 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Dynamic heat transfer modeling and parametric study of thermoelectric radiant cooling and heating panel system
ترجمه فارسی عنوان
مدل سازی انتقال حرارت دینامیک و مطالعه پارامتری سیستم خنک کننده و پانل های گرمایش تابشی و حرارتی
کلمات کلیدی
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی انرژی (عمومی)
چکیده انگلیسی


• Dynamic model of thermoelectric radiant panel system is established.
• The internal parameters of thermoelectric module are dynamically calculated in simulation.
• Both artificial neural networks model and system model are verified through experiment data.
• Optimized system structure is obtained through parametric study.

Radiant panel system can optimize indoor thermal comfort with lower energy consumption. The thermoelectric radiant panel (TERP) system is a new and effective prototype of radiant system using thermoelectric module (TEM) instead of conventional water pipes, as heat source. The TERP can realize more stable and easier system control as well as lower initial and operative cost. In this study, an improved system dynamic model was established by combining analytical system model and artificial neural networks (ANN) as well as the dynamic calculation functions of internal parameters of TEM. The double integral was used for the calculation of surface average temperature of TERP. The ANN model and system model were in good agreement with experiment data in both cooling and heating mode. In order to optimize the system design structure, parametric study was conducted in terms of the thickness of aluminum panel and insulation, as well as the arrangement of TEMs on the surface of radiant panel. It was found through simulation results that the optimum thickness of aluminum panel and insulation are respectively around 1–2 mm and 40–50 mm. In addition, TEMs should be uniformly installed on the surface of radiant panel and each TEM should stand at the central position of a square-shaped typical region with length around 0.387–0.548 m.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Energy Conversion and Management - Volume 124, 15 September 2016, Pages 504–516
نویسندگان
, , , , , ,