Abstract
- We derive energy savings factor through improved airflow performance and efficiency in a massively energy consuming high-density data center as well as individual design factor's effectiveness for overall, objective performance index.
- Standard module for analyzing IT server room's thermal efficiency is configured by a minimum of two cold aisle and two hot aisle.
- Four airflow performance metrics were computed with CFD modeling of 46 different design alternatives to evaluate the thermal environment in a typical data center module. Overall design adequacy is evaluated in consideration to individual effects.
Related Topics
Physical Sciences and Engineering
Energy
Renewable Energy, Sustainability and the Environment
Authors
Jinkyun Cho, Joonyoung Yang, Woopyoung Park,