Abstract
This paper presents figures for the small power equipment loads encountered by the Welsh School of Architecture in UK offices while undertaking a programme of research and monitoring into the energy efficiency of air-conditioning systems in use. The findings are based on surveys undertaken in 30 air-conditioned offices between April 2000 and October 2002. Peak small power equipment loads were calculated using the CIBSE nameplate-ratio method. The results show that the small power loads averaged 17.5 W/m2 with a range between 6 and 34 W/m2 of treated floor area. When normalised for occupancy the calculated peak small power equipment loads averaged 158 W per person, with a range between 124 and 229 W per person. Current industry guidance could lead to the overestimation of small power equipment loads by as much as 650%, ultimately resulting in increased capital and running costs of air-conditioning plant and reduced thermal comfort. A more accurate method of estimating peak small power equipment loads in UK office buildings is suggested based on occupant density.