Article ID Journal Published Year Pages File Type
10287956 Fire Safety Journal 2005 22 Pages PDF
Abstract
One purpose of the large-scale tests was to obtain new relevant gas temperature-time data from large-scale HGV fires in tunnels. There is presently a lack of such information for road tunnels. The maximum heat release rates produced by the four different fire loads varied between 66 and 202 MW resulting in maximum gas temperatures at the ceiling ranging between 1281 and 1365 °C. A comparison with literature values shows that the gas temperatures obtained here are uniformly higher than those obtained in other similar large-scale test series conducted using solid materials. A mathematical correlation of a temperature-time curve is given and this is the best representation of the measured temperature and a combination of frequently used temperature curves for tunnels (the HC curve and the RWS curve).
Related Topics
Physical Sciences and Engineering Engineering Civil and Structural Engineering
Authors
, ,