Article ID | Journal | Published Year | Pages | File Type |
---|---|---|---|---|
10294104 | Renewable Energy | 2011 | 6 Pages |
Abstract
Analysis of borehole thermal resistance is important for the standard sizing of ground heat exchanger (GHE). In this paper, a p-linear dimensionless average fluid temperature is proposed to estimate borehole thermal resistance. A p-linear dimensionless fluid temperature and p-linear dimensionless average fluid temperature are introduced, and the p-linear dimensionless fluid temperature is compared with theoretical dimensionless fluid temperature calculated by quasi-three-dimensional model for both single and double U-tubes. Results show that the p-linear dimensionless temperatures with parameters p â 0 and p = â1/2 are respectively in good agreement with the theoretical dimensionless fluid temperatures of single and double U-tubes. Therefore, the dimensionless logarithmic mean temperature for p â 0 and the dimensionless geometric mean temperature for p = â1/2 should respectively be adopted to reasonably estimate the thermal resistance of single and double U-tube boreholes.
Keywords
Related Topics
Physical Sciences and Engineering
Energy
Renewable Energy, Sustainability and the Environment
Authors
Ciyuan Du, Youming Chen,