Article ID | Journal | Published Year | Pages | File Type |
---|---|---|---|---|
10401322 | Electric Power Systems Research | 2011 | 10 Pages |
Abstract
This paper presents two new direct power control (DPC) strategies of three-phase grid connected VSIs for distributed generation, devised for the minimization of common-mode emissions. These strategies have been called DPC-EMC 1 (electro magnetically compatible) and DPC-EMC 2. Both of them reduce the common-mode emissions of the VSI by using either even or odd voltage vectors in each of the six sectors in which the grid voltage lies, without using any null vector. DPC-EMC 2 outperforms DPC-EMC 1 in terms ripple of the active and reactive power waveforms. These approaches permit the common-mode emissions to be reduced in comparison with the classic DPC algorithm, at the expense of an increase of the harmonic content of the injected current waveform which can be further corrected by a proper power line filter. An experimental comparison among the classic DPC, DPC-EMC 1 and DPC-EMC 2 is presented in terms of dynamic performance, harmonic content of the injected current and harmonic content of the common-mode voltage.
Keywords
Related Topics
Physical Sciences and Engineering
Energy
Energy Engineering and Power Technology
Authors
Maurizio Cirrincione, Marcello Pucci, Gianpaolo Vitale,