Article ID Journal Published Year Pages File Type
10401856 Electric Power Systems Research 2005 7 Pages PDF
Abstract
In this paper, an adaptive hysteresis band current controller is proposed for active power filter to eliminate harmonics and to compensate the reactive power of three-phase rectifier. The adaptive hysteresis band current controller, proposed by Bose [An adaptive hysteresis band current control technique of a voltage feed PWM inverter for machine drive system, IEEE Trans. Ind. Electron. 37 (5) (1990) 402-406] for electrical machine drives, is adapted to active power filter (APF). The adaptive hysteresis band current controller changes the hysteresis bandwidth according to modulation frequency, supply voltage, dc capacitor voltage and slope of the ic* reference compensator current wave. The hysteresis band current controller determines the switching signals of the APF, and the algorithm based on an extension of synchronous reference frame theory (d-q-0) is used to determine the suitable current reference signals. The results of simulation study of new APF control technique presented in this paper is found quite satisfactory to eliminate harmonics and reactive power components from utility current. All of the studies have been carried out through detail digital dynamic simulation using the MATLAB Simulink Power System Toolbox. The APF is found effective to meet IEEE 519 standard recommendations on harmonics levels.
Related Topics
Physical Sciences and Engineering Energy Energy Engineering and Power Technology
Authors
, ,