Article ID Journal Published Year Pages File Type
1057710 Journal of Environmental Management 2007 15 Pages PDF
Abstract

Fugitive methane emissions account for about 50% of the greenhouse gas (GHG) emissions from the Canadian conventional oil and gas sector. Sources include leaks in natural gas transmission facilities such as pipelines and compressor stations. There are three sources of methane emissions in a compressor station. The first is emissions resulting from incomplete combustion in the engine; the second is leaks in valves, flanges and other equipment in the building; and the third results from instrument venting. Fugitive methane emissions may be in low concentration relative to air, and thus cannot be destroyed by conventional combustion (below flammability limits of about 5–16%). The present study investigates the feasibility of capturing methane emissions from a compressor station. Computer modelling of the flow patterns of lean methane emissions inside the building is used to show the influence of doors, vents and leak location. Simulations show that for a typical building most fugitive methane exits through the ridge vent provided that the main doors remain closed. When the extraction rate through the ridge vent is controlled, the methane concentration is at acceptable levels for destruction in a catalytic flow reverse reactor, that is, in the range of 0.1–1% by volume.

Related Topics
Physical Sciences and Engineering Energy Renewable Energy, Sustainability and the Environment
Authors
, , ,