Abstract
The commercial sector consumes 8-50% of the total energy consumption for a few selected countries around the world. An energy audit was conducted in a Malaysian public hospital to identify energy using equipment and their energy consumption breakdown. Different energy saving measures have been identified and applied for electrical motors used in this hospital. It was estimated that this hospital consumed about 19,311Â MWÂ h for the year 2008. It was also estimated that about 212Â MWÂ h, 250Â MWÂ h and 317Â MWÂ h of annual energy can be saved using energy-efficient motors at 50%, 75% and 100% loads, respectively. In addition, use of variable speed drives are expected to save 1735Â MWÂ h, 4048Â MWÂ h and 6361Â MWÂ h of annual energy consumption for 20%, 40% and 60% speed reductions, respectively. It was found that the payback period for using high efficiency motors at different loads is less than a year which is economically very viable. However, the use of variable speed drives was found to be economically viable for larger motors for higher speed reductions. The study also found that a sizeable amount of emissions can be reduced for the different energy savings measures applied for electrical motors.
Related Topics
Physical Sciences and Engineering
Energy
Energy (General)
Authors
R. Saidur, M. Hasanuzzaman, S. Yogeswaran, H.A. Mohammed, M.S. Hossain,