Abstract
In this paper, a mathematical model for steady-state simulation of transcritical CO2 water-to-water heat pump system with an expander has been developed. It is used to simulate the performance of transcritical CO2 system with CO2 expander prototype. Simulated results are compared with experimental data to verify the accuracy of the simulation model. The comparison results show the average deviation of about 15% for COPc(cooling coefficient of performance) and COPh(heating coefficient of performance), about 17% for cooling and heating capacity at experimental high pressure ranges. With this model, which has been validated in a limited high pressure range, the influence of water mass flow rate and water inlet temperature of both evaporator and gas cooler on the performance of transcritical CO2 expander system is analyzed. The results show that decreasing inlet temperature and increasing mass flow rate of cooling water cannot only increase the system performance but also reduce the optimal heat rejection pressure, at which the maximum COP (coefficient of performance) can be obtained. For chilling water, increasing its inlet temperature and mass flow rate is favorable for increasing the system performance, while the optimal heat rejection pressure does not vary very much.
Related Topics
Physical Sciences and Engineering Energy Energy (General)
Authors
, , , ,