Abstract
⺠The LRM was used to evaluate the single control valve closure event. ⺠The purpose is to offer an updated analysis about the MCFL under the partial arc mode instead of FSAR's result. ⺠It is concluded that the 112% MCFL setting is the most limiting case. ⺠The MCFL setting actually used in SBPCS must be kept between 112% to 114% to gain the operational margin. ⺠The HFF index defined by the normalized heat flux can be used to predict the CPR change.