Article ID Journal Published Year Pages File Type
1732517 Energy 2014 8 Pages PDF
Abstract

•Innovative simplified correlation for counterflow cooling tower is proposed•Comparison between the new correlations and experimental data is conducted.•Comparison between the new correlations and others in the literature is conducted.•Example of how the correlation would be used is given.

This paper presents an innovative correlation associating the effectiveness (ε)(ε) of the cooling tower with its number of transfer unit (NTU) and vice versa. The new correlations can be used simply to predict the performance of wet counterflow cooling tower. Those correlations are based on solving heat and mass-transfer equation “enthalpy potential method” coupling with energy equations simultaneously. The validity of the correlations was checked by experimental data reported in the available literature. The results obtained from those new correlations showed a very good agreement with deviation less than 10% with those obtained from the literature for a temperature difference between the inlet water temperature and inlet air wet-bulb temperature (Twi−Wbti)(Twi−Wbti) equal to or less than 10 K. The main advantages of those correlations are: (1) its simplicity to be implemented through simple calculations of input parameters; (2) it provides helpful guidelines for optimization of cooling tower performance during its operation coupling with the thermal system at which the tower is connected.

Related Topics
Physical Sciences and Engineering Energy Energy (General)
Authors
, ,