Article ID Journal Published Year Pages File Type
1734246 Energy 2011 12 Pages PDF
Abstract
► The article introduces a novel thermally activated cooling concept - a combined cycle couples an ORC (organic Rankine cycle) and a VCC (vapor compression cycle). ► A systematic design study was conducted to investigate effects of a variety of cycle configurations on overall cycle COP. ► The combined cycle with cooling subcooling and recuperation can achieve overall cycle COP of 0.66, which is 22% above the basic cycle. ► The parametric design study identified expander isentropic efficiency, condensing temperature and boiling pressure to be the most critical parameters. ► Two advanced cycle configurations including dual-fluid system were proposed for future studies.
Related Topics
Physical Sciences and Engineering Energy Energy (General)
Authors
, , ,