Article ID | Journal | Published Year | Pages | File Type |
---|---|---|---|---|
1817879 | Physica C: Superconductivity and its Applications | 2013 | 7 Pages |
Abstract
The suitable introduction method of SN transition type superconducting fault current limiter (SNFCL) into a typical 6.6-kVdistribution system in Japan is described. A present distribution system is operated in the radial configuration and aged equipment with the isolated neutral system. An introduction of the FCLs into this system could expect to become a countermeasure against a short-circuit when introducing distributed generations in a future looped distribution system, the entire system will go into a blackout without any countermeasures, when a fault occurs within the looped system. But the introduction of the FCLs is expected to localize a blackout and to enhance the flexibility of a system configuration. In order to achieve the above-mentioned purposes of the introduction of the FCLs, the setting method of the parameters which a user should set is proposed using the transient analysis model of the SNFCL which we have ever developed.
Keywords
Related Topics
Physical Sciences and Engineering
Physics and Astronomy
Condensed Matter Physics
Authors
Hideyuki Kameda, Satoshi Uemura, Ataru Ichinose,