A method for calculating reactive power limit of wind farm comprised of doubly-fed induction generators (DFIG) is proposed. The reactive power limit of wind farm is the sum of reactive power limit of DFIGs which is calculated by the method considering static stability margin. Based on this, reactive power control of wind farm is discussed and proposed. The proposed reactive power control is divided into different control modes according to power factor of high voltage side in wind farm substation and voltage of low voltage side in point of interconnection(POI). In different control modes, different control objects are applied on reactive power regulation. After reactive power regulation is finished, some reactive power of wind farm should be released. At last, numerical test system is established, the result shows that the proposed method is effective to support voltage of POI