Article ID Journal Published Year Pages File Type
248729 Building and Environment 2011 9 Pages PDF
Abstract

ISO 7730 Standard classifies thermal environments in three categories as a function of the PMV range value, gradually decreasing according to the need of a lower dissatisfied percentage. It is noteworthy that the PMV value is greatly affected by the changes of its independent variables (air temperature, mean radiant temperature, air velocity, relative humidity, metabolic rate and clothing insulation); therefore the accuracy requirements of sensors for the measurement of environmental quantities as well the assessment of other parameters related to the activity and clothing appear a crucial matter. This work deals with a sensitivity analysis of PMV index to the accuracy of its six independent variables. Obtained results clearly show that the widths of PMV ranges fixed for each class in 7730 are near to the PMV uncertainty related to measuring devices accuracy, making often the environment classification a random operation.

Related Topics
Physical Sciences and Engineering Energy Renewable Energy, Sustainability and the Environment
Authors
, , ,