Article ID Journal Published Year Pages File Type
248866 Building and Environment 2010 9 Pages PDF
Abstract

In this paper, the results of performance analysis of a ground-assisted hybrid evaporative cooling system in Tehran have been discussed. A Ground Coupled Circuit (GCC) provides the necessary pre-cooling effects, enabling a Direct Evaporative Cooler (DEC) that cools the air even below its wet-bulb temperature. The GCC includes four vertical ground heat exchangers (GHE) which were arrayed in series configuration. In order to have an accurate prediction of the optimum performance of a GCC, a computational fluid dynamic simulation was performed. Simulation results revealed that the combination of GCC and DEC system could provide comfort condition whereas DEC alone did not. Based on the simulation results the cooling effectiveness of a hybrid system is more than 100%. Thus, this novel hybrid system could decrease the air temperature below the ambient wet-bulb temperature. This environmentally clean and energy efficient system can be considered as an alternative to the mechanical vapor compression systems.

Related Topics
Physical Sciences and Engineering Energy Renewable Energy, Sustainability and the Environment
Authors
, , ,