249923 | Building and Environment | 2008 | 8 Pages |
The weather in Baghdad, Iraq is hot dry in the summer while water is plentiful and cheap. These are conditions which encourage the use of evaporative cooling. A building with one space in it was used to test the effect of a roof pond which was ventilated mechanically for summer cooling. Thermal measurements were taken for the room in normal conditions without a pond, with a lone pond and no mechanical ventilation, and then finally with mechanically forced ventilation. The results showed a marked improvement in the space temperature with a significant reduction during the peak time outside temperatures at 3 O’clock reaching 6.0 °C between the room without the pond and with a ventilated one and 6.5° at 18:00 during peak inside temperatures. The study also showed that improvements would be better in real-life conditions where exterior wall area is less than the test room.