Article ID Journal Published Year Pages File Type
262461 Energy and Buildings 2015 10 Pages PDF
Abstract

•Supported mixed convection over partially thermally activated vertical TABS was experimentally studied.•It is not influenced upstream over thermally activated TABS if TABS is not fully thermally activated downstream.•Effect of founding was tested in simulation study of office room cooled with mixed convection.

This paper presents experimental study of supported mixed convection of two-dimensional wall jet over various thermal activation lengths of vertical TABS. It was found out that supported mixed convection upward the jet over vertical TABS is not influenced by thermally inactivated vertical TABS downwards of the wall jet. Practical consequences of this founding were after that tested using TRNSYS simulation tool in energy simulation study for contemporary modern office room having vertical TABS. Results show that office room can be sufficiently cooled by mixed convection even for TABS designs where only upper half of room wall is thermally activated by environmental high temperature cooling sources.

Related Topics
Physical Sciences and Engineering Energy Renewable Energy, Sustainability and the Environment
Authors
, , , , ,