Article ID Journal Published Year Pages File Type
262838 Energy and Buildings 2014 9 Pages PDF
Abstract

•Seasonal performance modeling based on EN14825 of a residential air/water heat pump for different climate zones.•Economic analysis of variable versus fixed compressor speed capacity control.•Optimization of component selection for both control schemes.•Discussion of sensitivity of results towards modeling assumptions.•Capacity control is cost competitive only for cold climate zones.

Adjusting capacity to changing demand by variable speed control is known to offer efficiency improvement over classical on/off control. With a total cost of ownership analysis the economic viability of both control schemes is assessed for residential air–water heat pumps operating in different climate zones. Component sizes are optimized for both control methods individually. Results show optimal compressor displacement volumes to be smaller for variable speed than for on/off control. The optimal ratio of evaporator to condenser size is smaller for the variable speed system. Variable speed control is shown to be uneconomic for space heating in warmer climate while for average climate cost-effectiveness depends on the economic framework. For colder climate variable speed control is the more profitable choice in all considered cases; savings of up to 5000 EUR compared to on/off control can be achieved within 15 years of operation.

Related Topics
Physical Sciences and Engineering Energy Renewable Energy, Sustainability and the Environment
Authors
, ,