Article ID Journal Published Year Pages File Type
263607 Energy and Buildings 2012 8 Pages PDF
Abstract

The water-intake temperature is a key factor affecting the system energy efficiency of an open-loop surface water source heat pump system (SWHPS). In addition to the conventional single-pipe water-intake design, we proposed two new design options that can improve SWHP efficiency. The numerical model that pertains to a SWHPS is presented and parameters such as the fluid-intake temperature and energy-saving rate of the heat pump system are analyzed and compared with experimental measurements. Our results demonstrate that on the basis of energy-saving rate, reducing the velocity of the water delivery has no significant influence while intake via multiple ports delivers superior efficiency. In conclusion, the water-intake design impacts on the SWHPS energy-saving rate because of its efficiency in drawing lower temperature water from a water retention body during summer. The method presented in this paper can provide a reference for a more detailed improvement on the energy performance of an open-loop SWHPS.

Graphical abstractFigure optionsDownload full-size imageDownload as PowerPoint slideHighlights► We model water-intake designs that supersede conventional single-pipe intake port. ► Cooling water temperature difference is inversely correlated to energy-saving rate. ► Energy efficiency is independent of water-intake velocity for single-pipe intake. ► Linear water-intake port delivers an optimal effect on energy-saving. ► This study detailed improvements on the performance of an open-loop SWHPS.

Related Topics
Physical Sciences and Engineering Energy Renewable Energy, Sustainability and the Environment
Authors
, , , , ,