Article ID Journal Published Year Pages File Type
264093 Energy and Buildings 2011 9 Pages PDF
Abstract

Probability density distribution profile of cooling load ratio is obtained by Parzen window density estimation method, which is used to describe the building cooling load variation. Based on the analysis of this profile, the optimal sequence control strategies (AI, AII and AIII) are presented. In order to optimize the COP of total chillers, the optimal load allocation control strategy B is presented. The optimal load allocation control strategy BI is presented to improve the strategy B for simplifying the process of the optimal calculation and maintaining stability of the system operating. Simulation results show that these optimal control strategies presented can save more power consumption of chillers operating than the original sequence control strategy. Comparing the strategy B, the strategy BI can avoid unnecessary switch on/off actions of chillers and decrease computational costs.

► The simulation model of an airport building and HVAC system is developed and calibrated. ► The optimal sequence control strategies (AI, AII and AIII) are presented. ► The optimal load allocation control strategy B is presented to optimize the total COP of chillers. ► The strategy BI is presented to improve the strategy B for simplifying the process of the optimal calculation and maintaining stability of the system operating.

Related Topics
Physical Sciences and Engineering Energy Renewable Energy, Sustainability and the Environment