Article ID Journal Published Year Pages File Type
302626 Renewable Energy 2008 6 Pages PDF
Abstract

A room-cooling system of 2 kW capacity fueled by wood pellets was designed, built and tested. The system was demonstrated during summer at the Yakushima Field Station of Kagoshima University, Japan. It contained a pellet feeder, a pellet burner, a heat exchanger, a lithium bromide–water absorption heat pump and a control unit. The volume of the test room was 36.9 m3 and ambient temperature 30 °C. The airflow temperature from the room unit was decreased to 16 °C by the system, and the room temperature could be successfully controlled to 24 °C steady state. Room heating in winter was also demonstrated. Since the air was heat exchanged, the overall energy efficiency of the cooling system was low at about 19%. However, the calculation based on the heat flow showed that the efficiency could be enhanced to about 75% by direct heating of the regenerator by the flue gas.

Related Topics
Physical Sciences and Engineering Energy Renewable Energy, Sustainability and the Environment
Authors
, , , , , ,