Article ID Journal Published Year Pages File Type
303093 Renewable Energy 2005 10 Pages PDF
Abstract

A hybrid system consisting of vapour compression unit, a liquid desiccant system, and a flat solar hot water collector were designed, fabricated and tested. This combination allowed for a separate control of humidity and temperature without energy penalty. Various packing heights of the absorber component were tested to determine the optimal performance of the combined unit. A 1000 mm packing height with cross-sectional area of 600×600 mm, proved to be the best height that gives promising improvements in the coefficient of performance of the vapour compression unit.

Related Topics
Physical Sciences and Engineering Energy Renewable Energy, Sustainability and the Environment