Article ID Journal Published Year Pages File Type
4434554 Atmospheric Pollution Research 2015 7 Pages PDF
Abstract

Indoor air pollution in university research laboratories may be important to building occupants, especially for those who work in the laboratories. In this study, indoor air quality (IAQ) and indoor environmental comfort were investigated in research laboratories of two departments at a university. PM2.5, PM10, TVOC (total volatile organic compounds), and CO concentrations, and three comfort variables which are temperature, relative humidity, and CO2 were measured. PM2.5 concentration was determined gravimetrically by collecting particles on glass fiber filters, whereas the remaining pollutants and comfort variables were measured using a monitoring device. IAQ measurements showed that levels of all pollutants were under the limits in both of the departments except for TVOC in one laboratory which had a mean concentration of 182 ppb. The comfort variables were in the comfort ranges for laboratories in both of the departments except for temperature in one laboratory with a mean value of 30 °C. In conclusion, measures are needed for extensive uses of organic solvents because ventilation may not be sufficient to keep VOC concentrations within the limits, and to provide thermal comfort.

Related Topics
Physical Sciences and Engineering Earth and Planetary Sciences Atmospheric Science