Article ID | Journal | Published Year | Pages | File Type |
---|---|---|---|---|
4919497 | Energy and Buildings | 2016 | 7 Pages |
Abstract
This paper presents an experimental study on a bilinear temperature control of a ground source heat pump (GSHP) integrated variable air volume (VAV) air-conditioning system, which may experience significant variations in the supply air temperature due to the frequent on/off switch of the ground source heat pump and the low thermal capacity at the air side. The bilinear control was realized in a building automation system (BAS) and applied to a test rig. The experimental results show that with an online estimation of the cooling load the bilinear control was able to maintain the space temperature at its set-point well and the control performance was superior to that of a conventional PI control. Therefore, the bilinear control has the potential to be used in GSHP integrated air-conditioning systems to improve the robustness and accuracy of the space temperature control.
Keywords
Related Topics
Physical Sciences and Engineering
Energy
Renewable Energy, Sustainability and the Environment
Authors
Jiajia Gao, Gongsheng Huang, Xinhua Xu,