A model for smoke filling in a large room was developed that considers entrainment into the horizontally spreading smoke under the ceiling. This was accomplished by incorporating a simple model for the spreading ceiling jet into the two-layer zone model. Here, the proposed model was validated by focusing on the horizontal smoke spread phase on the basis of the previous experimental data of smoke spread in a large office room. The calculated results were in good agreement with the experimental data. In addition, a case study on the smoke filling in a large room was conducted to clarify the characteristics of the proposed model. As a result, the proposed model can predict the underside of the smoke layer to be lower than the two-layer zone model.