Article ID | Journal | Published Year | Pages | File Type |
---|---|---|---|---|
4992990 | International Communications in Heat and Mass Transfer | 2017 | 9 Pages |
Abstract
The convective heat transfer, friction factor and effectiveness of different volume concentrations of Fe3O4 nanofluid flow in an inner tube of double pipe heat exchanger with return bend has been estimated experimentally and turbulent flow conditions. The test section used in this study is of double pipe type in which the inner tube diameter is 0.019Â m, the annulus tube diameter is 0.05Â m and the total length of inner tube is 5Â m. At a distance of 2.2Â m from the inlet of the inner tube the return bend is provided. The hot Fe3O4 nanofluid flows through an inner tube, where as the cold water flows through an annulus tube. The volume concentrations of the nanoparticles used in this study are 0.005%, 0.01%, 0.03% and 0.06% with Reynolds number range from 15,000 to 30,000. Based on the results, the Nusselt number enhancement is 14.7% for 0.06% volume concentration of nanofluid flow in an inner tube of heat exchanger at a Reynolds number of 30,000 when compared to base fluid data; the pumping penalty of nanofluid is <Â 10%. The effectiveness of heat exchanger for water and nanofluid flow is explained in terms of number of transfer units (NTU) in order to estimate the overall performance of the double pipe heat exchanger. New correlations for Nusselt number and friction factor have been developed based on the experimental data.
Related Topics
Physical Sciences and Engineering
Chemical Engineering
Fluid Flow and Transfer Processes
Authors
N.T. Ravi Kumar, P. Bhramara, Birhanu Mulat Addis, L. Syam Sundar, Manoj K. Singh, Antonio C.M. Sousa,