Article ID Journal Published Year Pages File Type
5012191 Energy Conversion and Management 2017 17 Pages PDF
Abstract
The results show that conventional VC systems resulted in an average increase in the ambient temperature in Beirut of 1.3 °C in day-time and 2.2 °C in night-time in the simulated period in the month of August. The electrical energy consumption of hybrid systems with IEC and HE systems was lower by 53% and 38% than VC systems, respectively. Compared to VC, HE systems increased the sensible waste heat by 10% while IEC systems decreased it by 2%. Compared to VC systems, IEC systems resulted in decrease of ambient temperature by 0.1-0.3 °C and HE systems increased the ambient temperature by 0.1-0.3 °C. The IEC system is recommended due to its high electricity savings and lower impact on the urban heat island compared to the conventional system.
Related Topics
Physical Sciences and Engineering Energy Energy (General)