Article ID | Journal | Published Year | Pages | File Type |
---|---|---|---|---|
5016939 | International Journal of Refrigeration | 2017 | 24 Pages |
Abstract
The Kigali amendment to the Montreal Protocol has highlighted the hydrofluorocarbons (HFCs) phase out as a priority to reduce the future global mean temperature increase. R134a is the most abundant HFC in the atmosphere and therefore it must be substituted using environmentally benign alternatives. In the short term, blends of HFCs and hydrofluoroolefins can replace R134a. This paper experimentally evaluates R450A (GWP of 547), a non-flammable mixture of R1234ze(E) and R134a, in an R134a small capacity refrigeration system. The controlled experimental conditions cover evaporating temperatures from â15 to 12.5â°C and condensing temperature of 25, 30 and 35â°C (36 tests in total for each refrigerant). The experimental results showed that with only a thermostatic expansion valve adjustment the average R450A cooling capacity and COP are 9.9% and 2.9% lower than those measured using R134a. Besides, the observed compressor discharge temperature values of R450A are not greater than that of R134a.
Keywords
Related Topics
Physical Sciences and Engineering
Engineering
Mechanical Engineering
Authors
Pavel Makhnatch, Adrián Mota-Babiloni, Rahmatollah Khodabandeh,