Article ID | Journal | Published Year | Pages | File Type |
---|---|---|---|---|
5017280 | International Journal of Refrigeration | 2017 | 29 Pages |
Abstract
The present work reports a numerical analysis of a single-phase supersonic ejector working with R134a as well as hydrofluoroolefin (HFO) refrigerants R1234yf and R1234ze(E). Comparisons were made regarding the ejector performances under varying operating conditions and refrigerant mixture proportions. The calculations have been then extended to an existing ejector heat driven refrigeration cycle (EHDRC). R1234yf appears to be a good candidate for drop-in replacement of R134a in a real EHDRC, while using R1234ze(E) would induce some modifications due to its thermodynamic properties. Maintaining the same pressure ratio for the ejector would lead on one hand to better entrainment ratio using R1234ze(E) and on the other hand to reduced coefficient of performance (COP) and cooling power by 4.2% and 26.6% in average, respectively. Using R1234yf under the same conditions induces a decrease of 5.2% for the entrainment ratio, 9.6% for the COP and 19.8% for the cooling power in average.
Keywords
Related Topics
Physical Sciences and Engineering
Engineering
Mechanical Engineering
Authors
Yu Fang, Sergio Croquer, Sébastien Poncet, Zine Aidoun, Yann Bartosiewicz,