Article ID Journal Published Year Pages File Type
5017297 International Journal of Refrigeration 2017 36 Pages PDF
Abstract
This paper proposed a universal virtual variable-speed compressor power (VVCP) sensor for VRF system based on 20-coefficient model. Compressor power can be obtained by the VVCP sensor using three input parameters (frequency, condensing temperature and evaporation temperature) which are measured by system itself. The performance of the proposed VVCP sensor is evaluated using experiments data. Experimental conditions include cooling, heating and non-standard refrigerant charge levels. The result shows that the mean square percentage errors (MSPE) are 9.9% under cooling conditions and 7.96% under heating conditions. The MSPE are 9.88% at steady state and 9.75% at dynamic state when the VVCP sensor is applied under nine different refrigerant charge levels. It demonstrated that the proposed VVCP sensor can obtain compressor power under cooling, heating and non-standard refrigerant charge levels, which could be applied to do operational monitoring and fault detection and diagnosis for VRF system at low cost.
Related Topics
Physical Sciences and Engineering Engineering Mechanical Engineering
Authors
, , , , , , , ,