Article ID Journal Published Year Pages File Type
5017335 International Journal of Refrigeration 2017 36 Pages PDF
Abstract
Thermodynamic investigations on the performance of the HVCR system, using CO2 as a refrigerant, are performed with energetic and exergetic methods, and the comparative analyses with the VCR system are conducted. Comprehensive effects of key operating parameters on the system performance are also studied. The results indicate that for the same cooling capacity, the coefficient of performance (COP) of the HVCR system shows 25% higher COP and the total mechanical power consumption is reduced by 20% than that of conventional VCR system, respectively. The performance characteristics of the proposed cycle show its application potential in cooling and air-conditioning.
Related Topics
Physical Sciences and Engineering Engineering Mechanical Engineering
Authors
, , , , , ,