Simulation results indicate the presence of mixing air between hot air and cold air and cause less efficient of the cooling process. Optimization is carried out by adding blanking panels, cold aisle containment, and changing the layout of the components and shelves. The result shows that the value of RCI achieved at 100% for RCIhigh and 99% for RCIlow. Meanwhile, the PUE value is reduced to 1.92. The energy used by cooling system is also reduced by 1.28kW.