Article ID Journal Published Year Pages File Type
5445236 Energy Procedia 2017 8 Pages PDF
Abstract
FACTS controllers incorporating energy storage device has the ability to operate in all the four quadrants and thereby increases the operational flexibility. In this work, the influence of SSSC supported by Energy Storage (SSSC-ES) on subsynchronous resonance (SSR), in a system provided with fixed series compensation is studied. Effect of SSSC-ES injecting constant real and reactive voltage into the network is analyzed. The sample system is adapted from IEEE FBM and the SSR analysis is carried out using bifurcation technique. Validation of results is done using eigenvalue and transient analysis.
Related Topics
Physical Sciences and Engineering Energy Energy (General)
Authors
, , ,