Article ID | Journal | Published Year | Pages | File Type |
---|---|---|---|---|
5471425 | Applied Mathematical Modelling | 2017 | 10 Pages |
Abstract
The experimental research has been carried out in two steps. In the first step, we designed and we studied in laboratory a mathematical model to reproduce a real situation of the fan insulation. In the second step, we made experimental investigations on the spot. Comparing the measured vibration amplitudes to those obtained on mathematical model, we identified a hidden connection near one of cassettes with coil springs. The hidden connection has appeared during the cassettes mounting and so was created a mechanical asymmetry. Due to this, the dangerous levels of vibration have occurred and it was caused a temporary shutdown of the fan. The process for detecting and eliminating the mounting nonconformities it is presented in the paper.
Keywords
Related Topics
Physical Sciences and Engineering
Engineering
Computational Mechanics
Authors
Nani Viorel-Mihai, Cires Ioan,