Article ID | Journal | Published Year | Pages | File Type |
---|---|---|---|---|
5475653 | Energy | 2017 | 53 Pages |
Abstract
The developed model predicted of the LDMC-C/DV system operational parameters such as the supply flow rate and temperature and the liquid desiccant concentration, flow rate, and inlet temperature that meet thermal comfort and air quality requirements. Extensive simulations were performed on a typical office load of 75 W/m2 to generate design charts of the system for three DV supply air temperatures of 18, 20, and 22 °C to identify the appropriate DV flow rate and inlet desiccant (CaCl2) solution temperature that provide comfort and air quality and ensures that condensation is unlikely to occur. The LDMC sensible and latent load removal from the space load is directly read off the charts.
Keywords
Related Topics
Physical Sciences and Engineering
Energy
Energy (General)
Authors
Mohamad Hout, Nesreen Ghaddar, Kamel Ghali, Nagham Ismail, Marco Simonetti, Gian Vincenzo Fracastoro, Joseph Virgone, Assaad Zoughaib,