Abstract
In this study, cooling tests on the semi-open loop GSHP system were performed and the thermal performance of the system was measured in each test. The developed numerical model was validated using the results of the cooling tests. Then, a sensitivity analysis was performed to evaluate the system performance under different operational and geological conditions during cooling operation. The results showed that in comparison with conventional GSHP operation, cooling coefficient of performance (COP) and system coefficient of performance (COPsys) can be enhanced by 13.1% and 6.6%, respectively, under fast groundwater flow conditions, as expected at the experimental site. In the absence of groundwater flow, the semi-open loop system is estimated to boost the cooling COP and COPsys by 101% and 62%, respectively, for cooling operations. Finally, an economic analysis was performed, considering the capital and running costs of the system and also the additional equipment costs associated with semi-open loop systems. The results of the economic analysis showed that water pumping and injection can reduce GSHP system costs by 22-36%.