Article ID Journal Published Year Pages File Type
652032 Experimental Thermal and Fluid Science 2011 9 Pages PDF
Abstract

Differently from most previous studies, the heat transfer and friction characteristics of the pure refrigerant HFC-134a during evaporation inside a vertical corrugated tube are experimentally investigated. The double tube test sections are 0.5 m long with refrigerant flowing in the inner tube and heating water flowing in the annulus. The inner tubes are one smooth tube and two corrugated tubes, which are constructed from smooth copper tube of 8.7 mm inner diameter. The test runs are performed at evaporating temperatures of 10, 15, and 20 °C, heat fluxes of 20, 25, and 30 kW/m2, and mass fluxes of 200, 300, and 400 kg/m2 s. The quality of the refrigerant in the test section is calculated using the temperature and pressure obtained from the experiment. The pressure drop across the test section is measured directly by a differential pressure transducer. The effects of heat flux, mass flux, and evaporation temperature on the heat transfer coefficient and two-phase friction factor are also discussed. It is found that the percentage increases of the heat transfer coefficient and the two-phase friction factor of the corrugated tubes compared with those of the smooth tube are approximately 0–10% and 70–140%, respectively.

Related Topics
Physical Sciences and Engineering Chemical Engineering Fluid Flow and Transfer Processes