•The CFD model with compact fan-assisted perforations has been established.•The parametric features of the fan-to-tile distance and straightening have been examined.•Cooling performance can be significantly improved by applying the flow straightening.•The main effect of the fan-to-tile distance is more significant than the interaction effect.
Raised floors with hot-aisle/cold-aisle configurations have grown to be a critical arrangement for data center cooling. However, more sophisticated techniques are still desired to achieve proper thermal management for improving energy effectiveness and efficiency. The application of fan-assisted perforations may yield a smarter cooling solution accommodating non-uniform power densities and heat load demands to optimize the cooling performance in raised-floor data centers. The present research includes the construction and thermal analysis of a basic raised floor with compact fan assisted perforations modeled using computational fluid dynamics (CFD). The flow straightening effect of the fan-assisted tile and the fan-to-tile distance were treated as the critical design aspects under investigation. The field cooling performance affected by the parametric variation were carefully discussed and compared. Moreover, a full factorial design was employed to obtain and verify the qualitative and quantitative characteristics of the main and interaction effects of the design variation. Well-constructed fan-assisted perforations may satisfy an advanced cooling solution to better manage and optimize the heat and mass transfer in data centers.