Article ID Journal Published Year Pages File Type
657954 International Journal of Heat and Mass Transfer 2013 13 Pages PDF
Abstract
A numerical analysis was carried out to study the thermal-hydraulic characteristics of a 3-D laminar in-lined and staggered plate-fin and tube heat exchangers with block type vortex generators (VG) mounted behind the tubes. In this study, the optimization of the VG span angle (θ) and the VG transverse location (Ly) was investigated numerically along with a simplified conjugate-gradient method (SCGM). The area reduction ratio using a vortex generator relative to the plain surface is the objective function to be maximized. A search for the optimum span angle (θ) and transverse location (Ly), ranging from 30° < θ < 60° and 2 mm < Ly < 20 mm, respectively, was performed. The effect of different inlet conditions, (Reynolds number ReDh = 400-1200), was also investigated. The results showed that the maximum area reduction ratios reached 14.9-25.5% combined with the optimal design of (θ, Ly) at ReDh = 400-1200 for the in-lined arrangement, and 7.9-13.6% of the maximum area reduction ratio was achieved for the staggered arrangement.
Related Topics
Physical Sciences and Engineering Chemical Engineering Fluid Flow and Transfer Processes
Authors
, , ,