658541 International Journal of Heat and Mass Transfer 2013 8 Pages PDF
Abstract

The purpose of this experimental investigation is to investigate the effects of fin pitch (i.e., fp of 2.4, 3.2, and 4.2 mm) on the air-side heat transfer performance and frictional characteristics of L-footed spiral fin-and-tube heat exchangers at high Reynolds numbers (Redc) of 4000–15,000. A determinant of the parallel cross-flow and the counter cross-flow is the flow arrangement of the test heat exchangers. Ambient air and hot water are used as a working fluid on the air- and the tube-side, respectively. The results indicate that the air-side heat transfer coefficient and Colburn factor are independent of fin pitch. However, fin pitch does have an influential effect on the average heat transfer rate, pressure drop, and friction factor. In terms of industrial applications, the correlation of the Colburn factor and friction factor are proposed for practical applications.

Related Topics
Physical Sciences and Engineering Chemical Engineering Fluid Flow and Transfer Processes