Article ID Journal Published Year Pages File Type
6699509 Building and Environment 2016 16 Pages PDF
Abstract
Occupants in naturally ventilated Indian offices were found to be more adaptive than the prevailing ASHRAE and EN models would suggest. According to the IMAC model, neutral temperature in naturally ventilated buildings varies from 19.6 to 28.5 °C for 30-day outdoor running mean air temperatures ranging from 12.5 to 31 °C. This is the first instance where a study proposes a single adaptive model for mixed mode buildings asserting its validity for both naturally ventilated and air-conditioned modes of operation in the building, with neutral temperature varying from 21.5 to 28.7 °C for 13-38.5 °C range of outdoor temperatures. For air-conditioned buildings, Fanger's static PMV model was found to consistently over-predict the sensation on the warmer side of the 7-point sensation scale.
Related Topics
Physical Sciences and Engineering Energy Renewable Energy, Sustainability and the Environment
Authors
, , , , ,