Article ID Journal Published Year Pages File Type
670332 International Journal of Thermal Sciences 2008 7 Pages PDF
Abstract

The objective of this paper is to present an experimental study on environment friendly vapour absorption refrigeration system of 1 kW capacity using R134a-DMAC as the working fluids. The system is designed and tested for various operating conditions using hot water as heat source. In this paper, performance of the fabricated system are outlined with respect to various operating parameters such as heat source, condenser, absorber and evaporator temperatures. The result indicates that at the sink and source temperatures of 30 and 80 °C respectively and a typical heat input of 4 kW, the system attained steady state in two hours. For this system an actual COP of 0.25 to 0.45 was obtained under the tested conditions. The study reveals the feasibility of using R134a-DMAC as working fluids in the absorption machines using low potential heat sources for various applications.

Related Topics
Physical Sciences and Engineering Chemical Engineering Fluid Flow and Transfer Processes