Article ID | Journal | Published Year | Pages | File Type |
---|---|---|---|---|
6732570 | Energy and Buildings | 2015 | 10 Pages |
Abstract
This paper presents a relatively new, simple and robust, method for air leakage testing. A thirteen-story multi-unit residential building was tested for air leakage before and after an enclosure retrofit. The building suites had a pre-retrofit NLA50 average of 6.77Â cm2/m2 and an average post-retrofit NLA50 of 2.82Â cm2/m2-a 58% betterment. The effect of the retrofit on air leakage rates was assessed and compared to other multi-unit residential buildings across Canada and USA. The case study building was significantly tighter than other multi-unit residential buildings included in published studies. Recommendations were made for field-testing procedures in order to maximize the potential for accurate measured flow characteristics. Field-testing for air-tightness needs to be standardized in order for useful comparative results to be generated in order to inform future research and operational considerations for the multi-unit residential building stock across North America.
Keywords
Related Topics
Physical Sciences and Engineering
Energy
Renewable Energy, Sustainability and the Environment
Authors
Robin Urquhart, Russell Richman, Graham Finch,