Article ID | Journal | Published Year | Pages | File Type |
---|---|---|---|---|
6732681 | Energy and Buildings | 2015 | 8 Pages |
Abstract
The embodied energy for the EAHE system was evaluated as 1663.88Â kWÂ h. The maximum heating potential and cooling potential of EAHE obtained in the months of January and May, respectively, were calculated as 191.06Â kWÂ h and 247.25Â kWÂ h. The total yearly energy output of EAHE system for air flow velocity of 5Â m/s was found as 1290.53Â kWÂ h. The EPBT of EAHE system was calculated as 1.29 years. The SEER for typical summer and winter months were calculated as 1.34 and 1.10, respectively. The CO2 emission mitigation potential and the total carbon credits earned from EAHE system were calculated as 101.30Â tonnes and Rs 1, 72,817.80 ($2837.60), respectively by considering its life span as 50 years.
Keywords
Related Topics
Physical Sciences and Engineering
Energy
Renewable Energy, Sustainability and the Environment
Authors
Trilok Singh Bisoniya, Anil Kumar, Prashant Baredar,