Article ID | Journal | Published Year | Pages | File Type |
---|---|---|---|---|
6734048 | Energy and Buildings | 2014 | 10 Pages |
Abstract
- First field experiments on stack effect induced by split type air-conditioners.
- Temperature rise of 10-13 °C over 20 storeys due to stack effect.
- Temperature rise of 9 °C due to “stuck effect”, caused by recirculating hot air.
- Measured on-coil temperatures of 50 °C for upper storeys.
- Significant performance reduction, COP reduced by 18% (stack only) 32% (combined).
Keywords
Related Topics
Physical Sciences and Engineering
Energy
Renewable Energy, Sustainability and the Environment
Authors
Marcel Bruelisauer, Forrest Meggers, Esmail Saber, Cheng Li, Hansjürg Leibundgut,