Article ID Journal Published Year Pages File Type
6739145 Engineering Structures 2018 9 Pages PDF
Abstract
In this study, quasi-static cyclic test was conducted for three 1/3-scale specimens of different precast concrete frame pier structure systems of an urban viaduct in Shanghai, China. Various connection deployment strategies were utilized for the specimens, in order to verify these precast concrete frame piers used in the real structure. Two of the specimens were of the same cap beam design, while the third one was with tie beam. The two frame piers with cap beam had the same column-footing connection (grouted splice sleeve coupler), but the column-cap connections were grouted splice sleeve coupler and grouted corrugated duct connection, respectively. The frame pier with cast-in-place tie beam, however, only kept the grouted splice sleeve coupler for column-footing connection. The cyclic test results showed similar seismic behavior of the two specimens with cap beam, whereas the specimen with tie beam exhibited less energy dissipation capacity. This indicated that the seismic performance differences among the specimens are mainly caused by different structure systems, and the two types of the connections behave similarly with little damage. Finite element models that were optimized by considering joint region behavior and bond-slip phenomena showed good agreement with the test results.
Related Topics
Physical Sciences and Engineering Earth and Planetary Sciences Geotechnical Engineering and Engineering Geology