Article ID | Journal | Published Year | Pages | File Type |
---|---|---|---|---|
6761357 | Nuclear Engineering and Design | 2015 | 12 Pages |
Abstract
After providing a detailed description of the fire scenarios and of the experimental apparatus, this paper focuses on the characteristic stages of the cabinet fire development, essentially based on the heat release rate time evolution of the fire. The effects of the confinement, of the outlet branch location, of the ventilation management and of the fire barrier on the fire source were then investigated. The reproducibility of electrical cabinet fires is also studied. A new model for complex fire source (applied in this study for open-door electrical cabinet fires) was then developed. This model was introduced in the zone code SYLVIA and the major features of the compartment fire experiments, such as characteristic heat release rate with effect of oxygen depletion and over-pressure peak were then calculated with a rather good agreement for this complex fire source (i.e. electrical cabinet).
Related Topics
Physical Sciences and Engineering
Energy
Energy Engineering and Power Technology
Authors
M. Coutin, W. Plumecocq, P. Zavaleta, L. Audouin,