Article ID Journal Published Year Pages File Type
6973237 Journal of Loss Prevention in the Process Industries 2015 10 Pages PDF
Abstract
The overpressure generated in a 10 L cylindrical vented vessel with an L/D of 2.8 was investigated, with end ignition opposite the vent, as a function of the vent static burst pressure, Pstat, from 35 to 450 mb. Three different Kv (V2/3/Av) of 3.6, 7.2 and 21.7 were investigated for 10% methane-air and 7.5% ethylene-air. It was shown that the dynamic burst pressure, Pburst, was higher than Pstat with a proportionality constant of 1.37. For 10% methane-air Pburst was the controlling peak pressure for K <∼8. This was contrary to the assumption that Pred > Pburst in the literature and in EU and US standards. For higher Kv the overpressure due to flow through the vent, Pfv, was the dominant overpressure and the static burst pressure was not additive to the external overpressure. Literature on the influence of Pstat at low Kv was shown to support the present finding and it is recommended that the influence of Pstat in gas venting standards is revised.
Related Topics
Physical Sciences and Engineering Chemical Engineering Chemical Health and Safety
Authors
, , ,